Connecting the air ducts
- We recommend the use of DIN 24245 folded spiral-seams ducts for the air ducts. If there isn't enough space for these ducts, flat channels made from metal or plastic can be used.
Installation suggestions
- In hall ceilings (entrances) and in suspended ceilings.
Thermal insulation
- The supply air and exhaust air ducts (“K1/K2/K3” variants with duct connection) in unheated areas must be thermally insulated to a thickness of at least 50 mm (mineral wool, Aeroflex®).
- Outside air and outgoing air ducts must be protected from the build-up of condensation through the use of impermeable thermal insulation to a thickness of at least 50 mm.