Adjustment exhaust air/supply air (EA/SA)
Parameters | Set value |
EA/SA adjustment RV ventilation level | + - 15 % |
EA/SA adjustment NV ventilation level | + - 15 % |
EA/SA adjustment IV ventilation level | + - 15 % |
Setting value ex factory = 0 %
Supply and exhaust air volumes must be balanced over the entire application area. Normally the fans automatically ensure a balance and no adjustment has to be undertaken. Nevertheless, if fan tolerances need balancing, the adjustment parameters can be used to adapt the supply air volumetric flow to that of the exhaust air.
Example: Supply air volumetric flow: measured excess = 20 m³/h. EA/SA adjustment, NV ventilation level must be set to xx % for the adjustment.
When setting NV, the control automatically also adjusts RV and IV. The percentage deviation for NV is transferred to RV and IV. A manual adjustment for RV and IV is also possible and the NV adjustment does not then change. A new adjustment of NV does however again result in an adjustment to RV and IV. Adjusting RV also changes the humidity protection ventilation.
The adjustment cannot result in values falling below or exceeding minimum and maximum values for fan supply voltages.