Ventilation time programme
Regular time programme/holiday time programme
The time programs are activated by the Auto time operating mode. The regular time programme is always activated. The holiday time programme can be activated with time limits by specifying a time range using the Start date for holiday time programme and End date for holiday time programme parameters. The Holiday time programme active note is present for the duration of the activated holiday time programme.
Parameters: Holiday time start
Setting value: Date entry
Parameters: Holiday time end
Setting value: Date entry
You can program a time-of-day programme with 6 time windows and assigned ventilation level/function for every day of the week. The time-of-day programmes can be programmed individually. Alternatively, they can be programmed for several days by activating the desired days of the week. Individual days can also be copied later on. The ventilation level/function activated by the weekly time programme remains active until it is replaced by another air level/function starting within the time program.
Setting options for regular time programme/holiday time programme
Day of the week | Switching point | Ventilation level/ | From |
Monday | 1 | ● Off | 00:00 |
Monday | 2 | ● Off | 00:00 |
Monday | 3 | ● Off | 00:00 |
Monday | 4 | ● Off | 00:00 |
Monday | 5 | ● Off | 00:00 |
Monday | 6 | ● Off | 00:00 |
* Default setting in time window 1:
Regular time programme = nominal ventilation
Holiday time programme = humidity protection ventilation