Humidity sensor operation (optional)

Rel. humidity limit value
Parameters: Humidity sensor operation
Setting value: stepped / linear

Parameters: Rel. humidity limit value min.
Setting value: 30 ... 35 ... 45 % r. h.

Parameters: Rel. humidity limit value max.
Setting value: 50 ... 70 ... 80 % r. h.

Stepped: Rel. humidity limit value max. for intensive ventilation. The maximum value always serves, independently from the set operating mode, as a switching point for dehumidification. The minimum value is not taken into account.

Linear: Rel. humidity limit value min./max. for intensive ventilation with linear humidity control in Auto Sensor operating mode. The maximum value always serves, independently from the set operating mode, as a switching point for dehumidification. The minimum limit value applies to reduced ventilation. Between RV and IV, regulation is linear, stepless and demand-driven.

Setting also applies to nominal ventilation for single control panel in solo mode and linear setting. The limit value settings apply to the humidity value (optional).