Configuration of sensor 3 / sensor 4
Conditions for connecting sensor 3 and sensor 4:
Parameters: Single control unit inactive
Parameters: Sensor 3 / sensor 4 configuration
Setting value: yes / no
Parameters: Sensor 3 / sensor 4 type
Setting value: CO2, VOC, r.h., digital, start/stop, night cooling, flush mode, motion detector.
The function of the original single control panel connection on the “RLS” terminal is changed to two more sensor connections:
- 0-10 V inputs on terminal “S1+” for sensor 3 and terminal “S2-” for sensor 4
- 12 V supply voltage on terminals LD1 - LD3
The supply voltage of sensors 1 and 2 can be used for 24 V sensors. Yes activates the connected external sensors named/specified by type. The name appears on the main control unit.
If the digital sensor type parameter is selected, the 12 V supply voltage can be looped via a pushbutton and returned to the associated 0-10 V input (S1+ or S2-) 6 Main menu settings. When the pushbutton is pressed, the ventilation unit switches to intermittent ventilation for the time stated under Duration of ventilation level. Once this time has elapsed, the ventilation unit switches back to the previously selected ventilation level.