Cleaning unit
Depending on the level of contamination, we recommend:
- annual visual inspection of the heat exchanger also cleaning if required.
- annual cleaning of inside.
- annual check and cleaning of condensation run-off and the siphon.
Cleaning the heat exchanger and ventilation unit
- Loosen service cover’s screws. Carefully remove service cover.
- Remove the hosing between the float switch and condensate tank.
- Remove condensate tank and crossbar.
- Loosen lateral guide rails.
- Remove punched tape on heat exchanger.
- Pull heat exchanger down and out of the unit.
- Clean heat exchanger: Vacuum the sensitive heat exchanger with a standard vacuum cleaner. Thoroughly flush enthalpy heat exchangers with water or soapy water, drip off and let them dry well.
- Replace the heat exchanger.
- Secure punched tape to fix heat exchanger in place.
- Slide lateral guide rails back against the heat exchanger and fix in place.
- Put cross bar and condensate tank back into the unit.
- Connect condensate tank with float switch of condensate lift pump.
- Check function/seal integrity of condensate tank.
- Close the central and two side service covers.
- Switch on the ventilation unit.