Axial wall fan

DAQ 71/4 Ex

Article number: 0073.0337
Manufacturer: MAICO
Axial wall fan with square wall plate, DN 710, three-phase AC, explosion-proof, nominal power 2.2 kW, medium:... more information
Application examples: explosion-proof industrial applications, Process exhaust air
Product data sheet
DAQ 71/4 Ex IM0021307.PNG Axial wall fan with square wall plate, DN 710, three-phase AC, explosion-proof, nominal power 2.2 kW, medium: gas
DAQ 71/4 Ex IM0017898.PNG Axial wall fan with square wall plate, DN 710, three-phase AC, explosion-proof, nominal power 2.2 kW, medium: gas

Characteristic curve

DAQ 71/4 Ex - Characteristic curve

Dimensioned drawing

DAQ 71/4 Ex - Dimensioned drawing [mm]

Technical data

DAQ 71/4 Ex - Technical data

Article DAQ 71/4 Ex
Model Differentiation in nominal widths and number of poles
Air flow volume 17.499 m³/h
Rotating speed 1.440 1/min
Impeller type axial
Speed controllable
Reversing capacity
Type of voltage Three-phase AC
Rated voltage 400 V
Frequency 50 Hz
Nominal output 2.200 W
Inom 5,5 A
Degree of protection IP 55
Insulation class F
Pole-changeable
Installation site Wall / ceiling
Installation position Horizontal
Material Sheet steel, galvanised
Housing material Steel
Colour Silver
Weight 35 kg
Weight including packaging 39 kg
Nominal size 710 mm
Width 850 mm
Height 465 mm
Depth 850 mm
Width with packaging 860 mm
Height with packaging 485 mm
Depth with packaging 860 mm
EX designation in accordance with the ATEX Directive Ex II 2 G
EX designation in accordance with standard Ex db IIB+H2 T4 Gb X / Ex h IIB+H2 T4 Gb X
Ta ambient temperature -20 °C ≤ Ta ≤ +40 °C
Operating mode S1
PTC DIN 44082 M 100
Temperature class T4
Packing unit 1 piece
Range C
GTIN (EAN) 4012799733379
Article number 0073.0337

 

63 Hz

125 Hz

250 Hz

500 Hz

1 kHz

2 kHz

4 kHz

8 kHz

Total

LWA5, S5 (dB(A))

58,3

71,3

83,3

86,3

92,3

94,3

88,3

79,3

80,1

LWA5= free inlet sound power level in dB.

Accessories

DAQ 71/4 Ex - Accessories

Specific accessories

Product type Name Art. No. Price*(EUR) Action
Machine protection relay thermistor TMS 0157.0992 on request
  • On the notes
Differential pressure switch DDEx 500 0157.0302 on request
  • On the notes

General accessories

Product type Name Art. No. Price*(EUR) Action
Shutter AS 71 Ex New development 0151.0410 on request
  • On the notes
Connection frame VRI 71 0073.0341 on request
  • On the notes
Protection against accidental contact SGSI 71 0073.0343 on request
  • On the notes

Product description

Productdescription

DAQ 71/4 Ex

short description

Axial wall fan with square wall plate, DN 710, three-phase AC, explosion-proof, nominal power 2.2 kW, medium: gas

Product description

Features

  • Axial wall fan for applications in areas subject to explosion hazards.
  • Explosion protection and approvals in accordance with ATEX.
  • Qualified for all gases and vapours of Ex group IIA and IIB and also for hydrogen.
  • Ex II 2 G Ex db IIB+H2 T4 Gb X / Ex II 2 G Ex h IIB+H2 T4 Gb X.
  • For usage temperatures of -20°C ≤ Ta ≤ +40°C.
  • MAICO Ex fans fulfil the safety requirements of European Directive 2014/34/EU for units and protective systems in potentially explosive atmospheres.
  • For zone 1 and 2.
  • Types of ignition protection: “d” – pressure-proof housing and “c” – constructional safety.
  • With square wall plate.
  • Powerful fan for large air volumes.
  • Housing and wall plate made of sheet steel.
  • Axial impellers made of glass-fibre reinforced, antistatic polyamide.

Air flow direction

  • The air flow direction is marked.
  • Standard exhaust air mode, air flow direction with air drawn across motor.

Motor

  • Asynchronous three-phase AC motors.
  • IP 55 degree of protection.
  • IE3 motor.
  • S1 operating mode (continuous operation).
  • Temperature class T4.
  • Speed-controllable with frequency converter.
  • Permissible frequency range for speed control with frequency converter is 20 Hz to 50 Hz.
  • The temperature in the fan motor is monitored by PTC thermistors. The PTC thermistors must be connected to a triggering system (safety device according to Directive 2014/34/EU), that separates the fan permanently from the power if the temperature gets too hot.

Electrical connection

  • Connection in the terminal box on the motor.
  • Cable screw connection, in Ex d version, included in the scope of delivery.

Special versions

  • The following special versions are available on request, at an extra cost:
    • Version for supply air mode with air flow direction blown across the motor.

Table of contents

Wiring diagram

DAQ 71/4 Ex - Wiring diagram



Predecessor - successor

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

On this website, technologies such as cookies and measurements of reach (targeting and tracking) are used (services). This means that personal information such as the IP address and browser information is processed to continuously improve our website as well as to display to you customised content that corresponds to your individual interests. You may of course influence the use of this information through the settings you choose. The settings you have chosen are stored in a necessary selection cookie. With the exception of the selection cookie mentioned above, technically non-essential cookies and measurements of reach are only used if you provide permission in advance by clicking “ACCEPT ALL AND CLOSE”. Details and options for customising your consent can be found under Data protection settings.

Here you can select a variety of different categories of services or cookies. By activating the corresponding “Statistics & analytics” checkbox and confirming “Save settings”, you can give your informed consent to the use of cookies for customisation purposes. At the bottom of the website under “Data protection settings”, you can change or revoke your consent and settings for the individual services at any time with effect for the future.

Necessary cookies are absolutely necessary for the operation of the website. Without these cookies, the website would not function properly.

These cookies and services collect and process data for statistics and analytics and thus enable further improvements of this website for users. Google Analytics and Google Adwords Conversion are used for this purpose. You will find a detailed description of such use in our Privacy Policy.

Save settings ACCEPT ALL AND CLOSE Data protection settings