Axial fan

DAS 90/4

Article number: 0083.0859
Manufacturer: MAICO
Delivery date on request
Axial fan, DN 900, 3-phase current
Application examples: Production facility, Assembly hall, Storage facility, Industrial building, Workplace
Product data sheet
DAS 90/4 IM0009980.PNG Axial fan, DN 900, 3-phase current

Characteristic curve

DAS 90/4 - Characteristic curve

Dimensioned drawing

DAS 90/4 - Dimensioned drawing [mm]

Number of holes: 16

Technical data

DAS 90/4 - Technical data

Article DAS 90/4
Model Steel ring
Air flow volume 45.000 m³/h
Air volumenom 22.300 m³/h / in opt. efficiency
Pressure pfs, nom 591 Pa / in opt. efficiency
Rotating speed nnom 1.480 1/min / in opt. efficiency
Rotating speed 1.470 1/min
Impeller type axial
Speed controllable
Reversing capacity
Type of voltage Three-phase AC
Rated voltage 400 V
Frequency 50 Hz
Nominal output 5.945 W / in opt. efficiency
Inom 11,8 A / in opt. efficiency
Imax 15,4 A
Degree of protection IP 55
Insulation class F
Installation site Wall
Installation position vertical
Material Sheet steel, varnished
Housing material Sheet steel, varnished
Colour grey
Weight 100 kg
Weight including packaging 162 kg
Nominal size 900 mm
Width 1.130 mm
Height 1.130 mm
Depth 655 mm
Width with packaging 1.300 mm
Height with packaging 1.300 mm
Depth with packaging 930 mm
Airstream temperature at nominal current 50 °C
Airstream temperature at IMax -20 °C up to 50 °C
Packing unit 1 piece
Range C
GTIN (EAN) 4012799838593
Article number 0083.0859
Article DAS 90/4
Total efficiency η 62 %
Measurement category C
Efficiency category static
Efficiency level N 63
VSD necessary No
Year of manufacture see rating plate
Manufacturer’s name / official registration number / manufacturer's place of establishment Maico Elektroapparate-Fabrik GmbH / Freiburg registration court, HRB 601233 / Villingen-Schwenningen
Art. No. 0083.0859
PBEP / Air volumeBEP / Pfs, BEP 5,945 kW / 22.300 m³/h / 591 Pa
nBEP 1.480 1/min
Specific ratio ≈ 1
Information about dismantling and disposal see mounting instructions
Information about installation, operation and repairs see mounting instructions
Objects used to measure efficiency which are not described by the measurement category -
IBEP 11,8 A
Sound power levelLWA7 98 dB(A)

 

63 Hz

125 Hz

250 Hz

500 Hz

1 kHz

2 kHz

4 kHz

8 kHz

Total

LWA7, S5 (dB(A))

66

77

94

91

92

90

87

82

98

LWA7= housing and free inlet sound power level in dB.

Accessories

DAS 90/4 - Accessories

Specific accessories

Product type Name Art. No. Price*(EUR) Action
Square wall plate QW 90 0053.0015 on request
  • On the notes

General accessories

Product type Name Art. No. Price*(EUR) Action
Shutter ARP 100 0151.0080 on request
  • On the notes
Frequency converter MFU 19 0157.1220 on request
  • On the notes

Product description

Productdescription

DAS 90/4

short description

Axial fan, DN 900, 3-phase current

Product description

Brief description

  • Axial fan with steel wall ring, in three-phase AC version.
  • For wall installation.
  • Protective grille on the intake side, painted.
  • 8- to 10-blade impellers made of glass fibre reinforced polyamide.
  • Protected against weathering by epoxy coating.
  • Designed for the temperature range -10 °C to +50 °C.
  • Fans meet the requirements of the European Ecodesign Directive (EC) No.327/2011 Directive 2009/125/EC.
  • Vibration-free running due to dynamically balanced impeller and motor (shaft-rotor), according to quality class 6.3, DIN ISO 1940, part 1.
  • High efficiency on the ventilation side, low operating noise.
  • Simple mounting by means of square wall plate (accessory).

Air flow direction

  • The air flow direction is marked.
  • For air extraction (clockwise rotation) only.

Three-phase AC motor

  • Asynchronous motor.
  • Not suitable for ventilating steam-saturated air.
  • Rated voltage 400 V, 50 Hz.
  • IP 55 degree of protection.
  • Speed-controllable, exception: DAS 71/8, DAS 80/6 and DAS 112/8. Units controllable via optional frequency converter, e.g. type MF
  • The fan motor must be secured against thermal overload by means of a current-dependent protection device. The protection device is to be provided by the customer.
  • Overload protection with motor protection switch provided by the customer.

Electrical connection

  • In terminal box on motor.

Safety information

  • A star / delta switch, to be supplied by the customer, must be used with fans with power consumption > 4 Kw, in order to limit the starting current.
  • The fan may be operated, with free air intake or discharge, only if the protection against accidental contact with the impeller is guaranteed to be in accordance with DIN EN ISO 13857, e.g., with Maico SG protective grille.
  • Not controllable with a transformer.

Table of contents

Wiring diagram

DAS 90/4 - Wiring diagram

S - Switch

to be supplied by customer

When using a star-delta switch: Remove bridges V2 - U2 - W2 on the DAS terminal strip.



Predecessor - successor

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

On this website, technologies such as cookies and measurements of reach (targeting and tracking) are used (services). This means that personal information such as the IP address and browser information is processed to continuously improve our website as well as to display to you customised content that corresponds to your individual interests. You may of course influence the use of this information through the settings you choose. The settings you have chosen are stored in a necessary selection cookie. With the exception of the selection cookie mentioned above, technically non-essential cookies and measurements of reach are only used if you provide permission in advance by clicking “ACCEPT ALL AND CLOSE”. Details and options for customising your consent can be found under Data protection settings.

Here you can select a variety of different categories of services or cookies. By activating the corresponding “Statistics & analytics” checkbox and confirming “Save settings”, you can give your informed consent to the use of cookies for customisation purposes. At the bottom of the website under “Data protection settings”, you can change or revoke your consent and settings for the individual services at any time with effect for the future.

Necessary cookies are absolutely necessary for the operation of the website. Without these cookies, the website would not function properly.

These cookies and services collect and process data for statistics and analytics and thus enable further improvements of this website for users. Google Analytics and Google Adwords Conversion are used for this purpose. You will find a detailed description of such use in our Privacy Policy.

Save settings ACCEPT ALL AND CLOSE Data protection settings