ER-UP/D installation, second room

6

Protective grille

7

Filter mat, filter class G2

8

Adapter

9

Suction duct, second room connection: flexible aluminium duct AFR 75/AFR 80

10

Plastic installation socket for second room extraction DN 75/80

13

Housing floor seal

37

Mounting support UPM 60/100 (2 items)

40

ER-MO expanded rubber

S

Housing segment

X4

Clamping band or steel threaded rod with duct clamp

  1. Cut out housing segment on the marking using a knife.
  2. The unit will be damaged and function impaired by incorrect air if the plastic socket is inserted incorrectly.

    Degree of protection is no longer guaranteed.

    1. Lift up housing floor seal near socket and insert installation socket. Reinsert housing floor seal in the correct position.
  3. Place installation socket in housing. The edge of the socket must click into place on the wall of the housing.
  4. Install housing as described above for single room.
  5. Connect suction duct with installation socket sealed for ventilation.
  6. Produce fixing holes for adapter and insert dowels.
  7. Connect adapter to suction duct, e.g. with cold-shrink tape.
  8. Secure adapter to the wall.
  9. Insert filter mat and locate the internal grille in the correct position.

With second room extraction, keep regulating plate somewhere safe for the final installation. This is needed to operate the ER 100 fan insert and is inserted in the cover.