Important information about plastering
Fire may spread if ER-UPB housing is incorrectly installed.
Any gap remaining between the housing and shaft/tiles must be fully sealed with non-flammable materials resistant to deformation.
- Minimum overlap required for the ventilation shaft (without tiles, etc.) in the area of the connection duct 10 mm.
- Max. compensable plaster overshoot 7 mm.
- Max. protruding housing edge 20 mm, can be compensated for with spacing frame DR 60/100.
- Installation at a depth of 50 to 100 mm can be compensated for with the two-part wall frame ER-MR.
- The gap remaining between the housing and shaft must be fully sealed with non-flammable materials that are resistant to deformation so that incorrect air is not drawn in.
- Joints between the housing and wall can be covered with cover frame ER-AR.