Permitted exhaust air systems
Exhaust air system | ER-UP/G | ER-UPD | ER-UPB |
---|---|---|---|
PAM-GLOBAL RML cast ventilation system * | no | yes** | yes*** |
Ceiling barrier system ** | yes* | no | no |
System with fire-proof shaft * | no | yes** | yes*** |
Air extraction system without fire protection ** | yes* | no | no |
* ER-UP/G can be used inside and outside the shaft, connection duct made from flexible aluminium duct, second room connection made from flexible aluminium duct.
** ER-UPD can be used inside and outside the shaft, connection duct made from steel folded spiral-seams duct, second room connection made from flexible aluminium duct.
*** ER-UPB can be used inside the shaft, connection duct made from flexible aluminium duct, second room connection made from steel folded spiral-seams duct.