ER-UP controls (circuit board types)
ER-UP fans are available in various models and with various unit properties. These depend on the control/circuit board type used in the fan insert.
The switching variants and functions suited to the circuit board type are described in these instructions. Tolerance of all time details max. + 20 %.
- Standard model
- VZ model: with start delay and overrun time.
- VZ 15 model with start delay and overrun time.
- VZC model with adjustable start delay and adjustable overrun time.
- F model: Barrier-free. With light control for rooms without windows (min. switch-on brightness 30 lx, max. switch-off brightness on unit 0.3 lx). With start delay (50 sec.) and overrun time (6 min.).
- G model: With base load circuit. Continuous operation at 35 m³/h, high speed (full load) can be switched with optional switch.
- GVZ model with base load circuit, start delay and overrun time, continuous operation at 35 m³/h, high speed (full load) can be switched with optional switch.
- I model with interval control. For manual operation with start delay and overrun time. Operating period can be set to between 0 and 15 hours with intervals of around 10 minutes. Interval control off if 0 hours is set (Ti setting screw in far left position). Interval control active if Ti setting screw is turned at least 1/4 of a turn to the right from the far left position.
- H model: Barrier-free. With humidity control. Overrun time controlled by program (min. 15 minutes at full load). Can also be operated manually with optional switch. Not suitable for second room air extraction.
- D model: In combination with three-step switch with 3 power levels: 35, 60 or 100 m³/h. Can be used in combination with supply air elements for controlled domestic ventilation.
- RC model with radio electronics: Use in radio-controlled ventilation system MAICO smart. Based on EnOcean technology. Network-compatible (master-slave) separate ER 100 RC operating instructions. On/Off using radio switch or radio control RLS RC. With 3 power levels 35, 60 or 100 m³/h.
Unit type | Circuit board type | Start delay [s] | Overrun time [min] | speed controllable | Mains cable [mm”] |
---|---|---|---|---|---|
ER 60 | Standard board |
|
| no | 3 x 1.5 |
ER 100 | Standard board |
|
| yes | 3 x 1.5 |
ER 60 VZ, ER 100 VZ | VZ circuit board | 50 | 6 | no | 5 x 1.5 |
ER 60 VZ 15, ER 100 VZ 15 | VZ 15 board | 50 | 15 | no | 5 x 1.5 |
ER 60 VZC, ER 100 VZC | VZ 24 C board | 0…150 | 1.5…24 | no | 5 x 1.5 |
ER 60 F, | F circuit board | 50 | 6 | no | 3 x 1.5 |
ER 60 G, | G board |
|
| no | 5 x 1.5 |
ER 60 GVZ, ER 100 GVZ | G board + VZ board |
|
| no | 5 x 1.5 |
ER 60 I, | VZI 10 board | 50* | 10* | no | 5 x 1.5 |
ER 60 H, | H board |
| 15 | no | 5 x 1.5 |
ER 100 D | Standard board |
|
| no | 5 x 1.5 |
ER 100 RC | RC circuit board |
| 15** | no | 3 x 1.5 |
(W) Factory setting
* Start delay and overrun time for manual operation, e.g. via light switch
** Overrun time only if unit is used with individual switch, without RLS RC room air control.