Fire protection shut-off device - ER-UPD and ER-UPB housing
3 | Metal shut-off shutter with release mechanism and yoke spring [3.1] |
4 | Soldered strut |
5 | Metal exhaust socket |
| * Shown without fire protection board |
The fire protection shut-off device is permanently closed if there is no soldered strut.
Air extraction is then no longer possible.
- Check that the soldered strut is inserted correctly before installation. The functionality of the release mechanism must be ensured so that the shut-off shutter also opens in normal operation.
Unpleasant smells from the main duct.
The fire protection shut-off device does not close fully sealed if incorrectly installed.
- Before installation, check and ensure that the installation position is correct and the release mechanism is fully functional.
Preparing the metal shut-off device with upwards air outlet direction
- Remove the fitted yoke spring. To do this, use pliers to pull yoke spring out of exhaust socket from above.
- Check and ensure that shut-off shutter is fully functional.
Preparing the metal shut-off device with air outlet direction to the right or left
No modifications needed.
- Check and ensure that shut-off shutter is fully functional.