Axial wall fan

DZQ 35/6 B

Article number: 0083.0122
Manufacturer: MAICO
Axial wall fan with square wall plate, DN 350, three-phase AC
Application examples: Production facility, Commercial premises, Garage, Building container, Storage facility
Product data sheet
DZQ 35/6 B IM0009977.PNG Axial wall fan with square wall plate, DN 350, three-phase AC

Characteristic curve

DZQ 35/6 B - Characteristic curve

Dimensioned drawing

DZQ 35/6 B - Dimensioned drawing [mm]

  1. Steel wall plate = EZQ/DZQ model
  2. Steel wall ring = EZS/DZS model

Technical data

DZQ 35/6 B - Technical data

Article DZQ 35/6 B
Model Square wall plate
Air flow volume 1.700 m³/h
Rotating speed 930 1/min
Impeller type axial
Speed controllable
Reversing capacity
Type of voltage Three-phase AC
Rated voltage 400 V
Frequency 50 Hz
Nominal output 75 W
Inom 0,17 A
Imax 0,17 A
Degree of protection IP 55
Insulation class B
Pole-changeable
Mains cable 7 x 1,5 mm²
Installation site Wall / Ceiling
Type of installation Surface-mounted
Installation position horizontal / vertical
Material Sheet steel, galvanised
Colour Silver
Weight 9 kg
Weight including packaging 10,79 kg
Nominal size 350 mm
Width 525 mm
Height 525 mm
Depth 244 mm
Width with packaging 540 mm
Height with packaging 540 mm
Depth with packaging 330 mm
Airstream temperature at nominal current -20 °C up to 60 °C
Airstream temperature at IMax -20 °C up to 60 °C
Packing unit 1 piece
Range C
GTIN (EAN) 4012799831228
Article number 0083.0122

 

63 Hz

125 Hz

250 Hz

500 Hz

1 kHz

2 kHz

4 kHz

8 kHz

Total

LWA7, S1 (dB(A))

33

LWA7, S2 (dB(A))

45

LWA7, S3 (dB(A))

52

LWA7, S4 (dB(A))

55

LWA7, S5 (dB(A))

27

39

44

49

53

55

48

34

58

LWA8, S1 (dB(A))

36

LWA8, S2 (dB(A))

45

LWA8, S3 (dB(A))

51

LWA8, S4 (dB(A))

67

LWA8, S5 (dB(A))

37

43

48

51

64

65

67

64

71

LWA7= housing and free inlet sound power level in dB.

LWA8= housing and free outlet sound power level in dB.

Accessories

DZQ 35/6 B - Accessories

General accessories

Product type Name Art. No. Price*(EUR) Action
Shutter AS 35 0151.0333 on request
  • On the notes
Connection frame ZVR 35 0093.0194 on request
  • On the notes
Shutter, manual RS 35 0151.0341 on request
  • On the notes
Servomotor MS 2 0093.0403 on request
  • On the notes
External grille MLA 35 0151.0114 on request
  • On the notes
External grille MLZ 35 0151.0104 on request
  • On the notes
Extension sleeve VH 35 0055.0033 on request
  • On the notes
Internal grille IG 35 0059.0174 on request
  • On the notes
Main switch, service switch HS 3 0157.0736 on request
  • On the notes
Rotary switch DS 10 0157.0410 on request
  • On the notes
Reversing switch W 1 0157.0101 on request
  • On the notes
Reversing switch WU 1 Discontinued product 0157.0102 on request
  • On the notes
Motor protection switch MV 16-1 0157.1658 on request
  • On the notes
Motor protection switch MV 25-1 0157.1659 on request
  • On the notes
Contactor US 16 T 0157.0769 on request
  • On the notes
5-step transformer TR 0,4-2 0157.0147 on request
  • On the notes
5-step transformer, control cabinet TR 0,8 S-2 0157.0151 on request
  • On the notes
5-step switch for TRE...S -2/ TR...S-2 5-step transformers DSS 20 0157.0750 on request
  • On the notes
Thermostat THR 10-1 0157.0191 on request
  • On the notes
Thermostat TH 10 0157.0764 on request
  • On the notes
Thermostat TH 16 0157.0748 on request
  • On the notes
Hygrostat HY 230 0157.0126 on request
  • On the notes
Hygrostat HY 230 I 0157.0127 on request
  • On the notes
Air quality controller EAQ 10/1 Discontinued product 0157.0777 on request
  • On the notes
Thermostat THR 10 No longer available for delivery 0157.0774 on request
  • On the notes
Hygrostat HY 10 AP No longer available for delivery 0157.0358 on request
  • On the notes
Hygrostat HY 10 UP No longer available for delivery 0157.0357 on request
  • On the notes
Motor protection switch MV 25 No longer available for delivery 0157.0712 on request
  • On the notes

Product description

Productdescription

DZQ 35/6 B

short description

Axial wall fan with square wall plate, DN 350, three-phase AC

Product description

Three-phase AC model

  • Axial wall fan with square wall plate, in three-phase AC version.

Brief description

  • For surface mounting.
  • Protective grille on the intake side, protection against accidental contact in accordance with DIN EN ISO 13857.
  • 8-blade impellers made of glass fibre reinforced polyamide
  • Thermal overload protection as a standard feature.
  • Fans meet the requirements of the European Ecodesign Directive (EC) No.327/2011 Directive 2009/125/EC.
  • Vibration-free running due to dynamically balanced impeller and motor (shaft-rotor), according to quality class 6.3, DIN ISO 1940, part 1.
  • High efficiency on the ventilation side, low operating noise.
  • Increased durability due to high-quality materials such as quiet ball bearings.
  • Fans are maintenance-free.
  • Installation for ventilation and air extraction possible in any position.

Air flow direction

  • The air flow direction is marked.
  • Standard exhaust air mode, air flow direction with air drawn across motor.

Three-phase AC motor

  • DZQ/DZS type series.
  • Asynchronous motor.
  • Not suitable for ventilating steam-saturated air.
  • Rated voltage 400 V, 50 Hz.
  • IP 55 degree of protection. Exception for type DZQ ... D IP 54.
  • Speed-controllable. Exception for type DZQ 40/2 B and DZS 40/2 B.
  • Units can be switched in steps with an optional 5-step transformer.
  • Reversible.
  • Reversing mode: The volumetric flow is reduced by approx. 35 % with abnormal air flow direction.
  • Thermal overload protection as a standard feature. Exception for type DZQ/DZS 25/4 D and pole-changeable axial duct fans, available on request.
  • Potential-free terminal connections, which must be connected, e.g., to an MV 25-1 motor protection switch or the control circuit of a contactor.
  • Pole-changeable fans: Ensure overload protection is guaranteed by a motor protection switch provided by the customer.
  • Pole-changeable motors with speed ratios of 8/4 or 4/2 have a Dahlander pole-changing circuit.

Electrical connection

  • On terminal block in end cover of the motor.

Safety information

  • The fan may be operated only if the protection against accidental contact with the impeller is guaranteed to be in accordance with DIN EN ISO 13857, e.g., with Maico SG protective grille.

Special versions

  • The following special versions are available on request, at an extra cost:
    • Special voltages and frequencies.
    • Single-phase motors with thermal contacts or PTC thermistor, potential-free terminal connection.
    • Condensation drainage holes.
    • Fans with enhanced anti-corrosion protection.
    • Impellers made of aluminium.
  • Information on operation at temperatures occasionally below -20°C available upon request.
  • If operating with frequency converters, the factory must be consulted.
  • Feasibility must be checked in each case.

Table of contents

Wiring diagram

DZQ 35/6 B - Wiring diagram

DZQ/DZS/DZF..B standard (right-hand operation, 1 speed)

SC - Protection contact

TK - Thermal contact



DZQ/DZS/DZF..B standard (left-hand operation, 1 speed)

SC - Protection contact

TK - Thermal contact













Predecessor - successor

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

On this website, technologies such as cookies and measurements of reach (targeting and tracking) are used (services). This means that personal information such as the IP address and browser information is processed to continuously improve our website as well as to display to you customised content that corresponds to your individual interests. You may of course influence the use of this information through the settings you choose. The settings you have chosen are stored in a necessary selection cookie. With the exception of the selection cookie mentioned above, technically non-essential cookies and measurements of reach are only used if you provide permission in advance by clicking “ACCEPT ALL AND CLOSE”. Details and options for customising your consent can be found under Data protection settings.

Here you can select a variety of different categories of services or cookies. By activating the corresponding “Statistics & analytics” checkbox and confirming “Save settings”, you can give your informed consent to the use of cookies for customisation purposes. At the bottom of the website under “Data protection settings”, you can change or revoke your consent and settings for the individual services at any time with effect for the future.

Necessary cookies are absolutely necessary for the operation of the website. Without these cookies, the website would not function properly.

These cookies and services collect and process data for statistics and analytics and thus enable further improvements of this website for users. Google Analytics and Google Adwords Conversion are used for this purpose. You will find a detailed description of such use in our Privacy Policy.

Save settings ACCEPT ALL AND CLOSE Data protection settings