Compact box

ECR 16 EC

No longer available for delivery
Article number: 0080.0575
Manufacturer: MAICO
Compact supply air device with integrated electrical air heater, EC motor, filter and controller, DN 160
Application examples: Workplace, Doctor's practice, Day room, Fitness room, Restaurant
Product data sheet
ECR 16 EC IM0018067.PNG Compact supply air device with integrated electrical air heater, EC motor, filter and controller, DN 160

Characteristic curve

ECR 16 EC - Characteristic curve

  1. Auxiliary characteristics curves for control voltage 5 V, 7 V and 10 V

Dimensioned drawing

ECR 16 EC - Dimensioned drawing [mm]

Technical data

ECR 16 EC - Technical data

Article ECR 16 EC
Number of ventilation levels 3
Air flow volume 580 m³/h
Rotating speed 3.650 1/min
Speed controllable
Rated voltage 230 V
Frequency 50 Hz
Nominal output 3.124 W
Inom 0,9 A
Inom fan 0,9 A
Imax 0,9 A
IMax total 13,9 A
Degree of protection for motor IP 33
Insulation class F
Pole-changeable
Installation position vertical / horizontal
Material Sheet steel, galvanised
Colour Silver
Weight 28,76 kg
Weight including packaging 30,62 kg
Filter class ISO ePM10 ≥ 50 % (M5)
Nominal size 160 mm
Width 403 mm
Height 346 mm
Depth 786 mm
Width with packaging 500 mm
Height with packaging 380 mm
Depth with packaging 820 mm
Heater power rating 3.000 W
Packing unit 1 piece
Range E
GTIN (EAN) 4012799805755
Article number 0080.0575

 

63 Hz

125 Hz

250 Hz

500 Hz

1 kHz

2 kHz

4 kHz

8 kHz

Total

LWA2, low (dB(A))

38

52

53

49

44

45

40

35

57

LWA2, medium (dB(A))

37

48

48

48

42

43

38

32

54

LWA2, high (dB(A))

36

47

50

52

46

46

39

33

56

LWA5, low (dB(A))

40

62

62

59

62

60

55

51

68

LWA5, medium (dB(A))

38

59

56

56

60

57

53

51

65

LWA5, high (dB(A))

36

56

58

60

63

60

55

52

68

LWA6, low (dB(A))

39

58

61

61

66

66

62

55

71

LWA6, medium (dB(A))

38

54

56

59

63

64

60

54

69

LWA6, high (dB(A))

42

52

57

66

66

66

63

58

72

LWA2= housing sound power level in dB.

LWA5= free inlet sound power level in dB.

LWA6= free outlet sound power level in dB.

Accessories

ECR 16 EC - Accessories

Specific accessories

General accessories

Product description

Productdescription

ECR 16 EC

short description

Compact supply air device with integrated electrical air heater, EC motor, filter and controller, DN 160

Product description

Features

  • Space-saving compact unit consisting of ideally matched components:
    • Fan
    • Air filter
    • Electric air heater
  • With control for constant supply air temperature or room temperature.
  • With sound-absorbing rock wool, laminated with silk glass, and double-walled housing for minimum noise level and the best thermal insulation.
  • Air filter replacement in seconds without tools.
  • Impeller with blades curved to the rear for optimised efficiency.
  • Removable cover with clip-locks.
  • Inlet and outlet side connection socket for direct installation in ventilation ducts.
  • Time-saving mounting thanks to mounting tracks.
  • With automatic fan overrun to protect against overheating.
  • Can be switched on/off using external potential-free contact.
  • IP 33 degree of protection.

Electric air heater

  • Electric air heater is positioned downstream of the fan in the air flow.
  • Closed tubular radiator made from stainless steel.
  • With temperature sensor in flow direction behind the air heater with radiation protection plate.
  • If the heating elements are subject to thermal overload, a thermal contact interrupts the circuit.

Control unit

  • Separate control unit and 10 m control cable included in the scope of delivery.
  • Room temperature sensor integrated in control unit.
  • Option of room or supply air temperature control.
  • 3 ventilation levels.
  • Function keys for:
    • Unit on/off
    • Fan speed control
    • Increase/reduce setpoint temperature
    • Switching between automatic/manual mode
  • Display of:
    • speed level
    • Nominal and supply air temperature
    • Operation/fault with error code
  • Electronic filter monitoring with filter change warning displayed on the control unit.
  • With output for controlling a separate shutter.
  • With integrated timer with daily and weekly program for controlling the switch-on times for each individual day of the week.

Motor

  • EC DC motor.
  • Robust motor with ball bearings, maintenance-free.
  • Thermal overload protection as a standard feature.

Table of contents

Wiring diagram

ECR 16 EC - Wiring diagram

Predecessor - successor

ECR 16 EC - Predecessor

Product type Name Art. No. Action
Compact box ECR 16 No longer available for delivery 0080.0561
  • On the notes

ECR 16 EC - Successor

Product type Name Art. No. Action
Compact box ECR 16-2 EC 0080.0775
  • On the notes

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

On this website, technologies such as cookies and measurements of reach (targeting and tracking) are used (services). This means that personal information such as the IP address and browser information is processed to continuously improve our website as well as to display to you customised content that corresponds to your individual interests. You may of course influence the use of this information through the settings you choose. The settings you have chosen are stored in a necessary selection cookie. With the exception of the selection cookie mentioned above, technically non-essential cookies and measurements of reach are only used if you provide permission in advance by clicking “ACCEPT ALL AND CLOSE”. Details and options for customising your consent can be found under Data protection settings.

Here you can select a variety of different categories of services or cookies. By activating the corresponding “Statistics & analytics” checkbox and confirming “Save settings”, you can give your informed consent to the use of cookies for customisation purposes. At the bottom of the website under “Data protection settings”, you can change or revoke your consent and settings for the individual services at any time with effect for the future.

Necessary cookies are absolutely necessary for the operation of the website. Without these cookies, the website would not function properly.

These cookies and services collect and process data for statistics and analytics and thus enable further improvements of this website for users. Google Analytics and Google Adwords Conversion are used for this purpose. You will find a detailed description of such use in our Privacy Policy.

Save settings ACCEPT ALL AND CLOSE Data protection settings