Electrical air heater

DHP 25-16

Article number: 0082.0093
Manufacturer: MAICO
Electric air heater, three-phase AC, channel dimensions 500 mm x 300 mm

Product data sheet
DHP 25-16 IM0009880.PNG Electric air heater, three-phase AC, channel dimensions 500 mm x 300 mm

Characteristic curve

DHP 25-16 - Characteristic curve Pressure losses

  1. DHP 25-16
  2. DHP 22-9, DHP 28-16
  3. DHP 31-28
  4. DHP 31-16

DHP 25-16 - Characteristic curve Temperature rise

Dimensioned drawing

DHP 25-16 - Dimensioned drawing [mm]

A: 500 mm
B: 300 mm
C: 520 mm
D: 320 mm
E: 639 mm
F: 338 mm

Technical data

DHP 25-16 - Technical data

Article DHP 25-16
Min. flow velocity 1,5 m/s
Type of voltage Three-phase AC
Rated voltage 400 V
Frequency 50 Hz
Imax 23,1 A
Degree of protection IP 43
Installation inside and outside
Installation site Channel
Installation position horizontal / vertical
Housing material Sheet steel, galvanised
Weight 13,59 kg
Weight including packaging 15,05 kg
Channel dimension 500 mm x 300 mm
Width 639 mm
Height 338 mm
Depth 370 mm
Width with packaging 695 mm
Height with packaging 410 mm
Depth with packaging 400 mm
Air heater type electrical
Heater power rating 16.000 W
Packing unit 1 piece
Range D
GTIN (EAN) 4012799820932
Article number 0082.0093

Accessories / Accessories of

DHP 25-16 - Accessories / Accessories of

Specific accessories

General accessories

Product type Name Art. No. Price*(EUR) Action
Contactor US 16 T 0157.0769 on request
  • On the notes

is a general accessory of

Product type Name Art. No. Price*(EUR) Action
Channel fan EPK, DPK channel fans, 500 × 300 - - -

Product description

Productdescription

DHP 25-16

short description

Electric air heater, three-phase AC, channel dimensions 500 mm x 300 mm

Product description

  • Electrical air heater for ventilation systems.
  • Flanges on both sides for installation in square ventilation channels.
  • With non-glowing stainless steel tubular radiators.
  • Heater power rating linearly adjustable.
  • Operate with DTL 24 P temperature control system (see accessories).
  • Recommended accessories: FL channel sensor or FR room sensor, LW 9 air flow monitor, TFP ... air filter, US 16 T contactor, DTL 2 P-L (at 16.5 kW to 30 kW).

Installation instructions

  • Mount the water-air heater on the fan's pressure side in order to prevent fan motor overheating. An arrow marked on the housing shows the default air direction through the electrical air heater.
  • Mount a 1 m to 1.5 m long air duct fitting between fan and electrical air heater to ensure optimum inflow to the electrical air heater.
  • Inflow speed can be controlled using an LW 9 air flow monitor.
  • If the inflow speed falls below 1.5 m/s, the electrical air heater must be switched off.

Safety instructions

  • Increased danger of fire if tubular radiators are dirty. Install TFP air filter.
  • With 2 temperature limiters switching independently of each other.
  • Minimum distance to inflammable material: 300 mm (if distance is less, install appropriate insulation).

Table of contents

Wiring diagram

DHP 25-16 - Wiring diagram

DHP with EPK / DPK and DTL 24 P

S1 system off

S2 system on

L1 control light system on

K1 contactor US 16

K2/K3 contactor to be supplied by the customer

DPK..B centrifugal fan, DPK model series

EPK..B centrifugal fan, EPK model series

LW 9 air flow monitor (relay picks up with air flow)

DHP.. DHP 28-28.31-28 air heater

F1 temperature limiter

F2 safety temperature limiter

DTL 24 P electronic temperature controller

DTL 2 P-L basic power board for DTL 24 P

P1 setpoint generator DTL 24 P

S3 night reduction 4 K

FR 30 P room sensor with external setpoint generator

FL 30 P supply air channel sensor



DHP with EPK / DPK and DTL 24 P

S1 system off

S2 system on

L1 control light system on

K1 contactor US 16

K2/K3 contactor to be supplied by the customer

DPK..B centrifugal fan, DPK model series

EPK..B centrifugal fan, EPK model series

LW 9 air flow monitor (relay picks up with air flow)

DHP.. DHP 28-28.31-28 air heater

F1 temperature limiter

F2 safety temperature limiter

DTL 24 P electronic temperature controller

DTL 2 P-L basic power board for DTL 24 P

P1 setpoint generator DTL 24 P

S3 night reduction 4 K

FR 30 P room sensor with external setpoint generator

FL 30 P supply air channel sensor



Predecessor - successor

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

On this website, technologies such as cookies and measurements of reach (targeting and tracking) are used (services). This means that personal information such as the IP address and browser information is processed to continuously improve our website as well as to display to you customised content that corresponds to your individual interests. You may of course influence the use of this information through the settings you choose. The settings you have chosen are stored in a necessary selection cookie. With the exception of the selection cookie mentioned above, technically non-essential cookies and measurements of reach are only used if you provide permission in advance by clicking “ACCEPT ALL AND CLOSE”. Details and options for customising your consent can be found under Data protection settings.

Here you can select a variety of different categories of services or cookies. By activating the corresponding “Statistics & analytics” checkbox and confirming “Save settings”, you can give your informed consent to the use of cookies for customisation purposes. At the bottom of the website under “Data protection settings”, you can change or revoke your consent and settings for the individual services at any time with effect for the future.

Necessary cookies are absolutely necessary for the operation of the website. Without these cookies, the website would not function properly.

These cookies and services collect and process data for statistics and analytics and thus enable further improvements of this website for users. Google Analytics and Google Adwords Conversion are used for this purpose. You will find a detailed description of such use in our Privacy Policy.

Save settings ACCEPT ALL AND CLOSE Data protection settings