Aeronom room air system

WRG 300 WP

No longer available for delivery
Article number: 0082.0041
Manufacturer: MAICO
Compact ventilation system with heat recovery and heat pump

Product data sheet
WRG 300 WP IM0022790.PNG Compact ventilation system with heat recovery and heat pump

Characteristic curve

WRG 300 WP - Characteristic curve

WRG 300 WP - Characteristic curve

Dimensioned drawing

WRG 300 WP - Dimensioned drawing [mm]

  1. NW 150 mm outgoing air
  2. NW 150 mm outside air
  3. NW 150 mm exhaust air
  4. NW 150 mm supply air
  5. Electrical connection
  6. Condensation connection
  7. WPK only: Additional condensation connection

Technical data

WRG 300 WP - Technical data

Article WRG 300 WP
Air flow volume 320 m³/h / System pressure at 150 Pa
Power consumption 40 W / 295 W / 440 W / Power consumption measured at kwl
Imax 3 A / strom-kwl
Degree of protection IP 00
Colour white-grey
Weight 57
Heater power rating 2.010 W
Heat pump Air/air
Packing unit 1 piece
Range D
GTIN (EAN) 4012799820413
Article number 0082.0041

 

63 Hz

125 Hz

250 Hz

500 Hz

1 kHz

2 kHz

4 kHz

8 kHz

Total

LWA2, high (dB(A))

30

44

51

49

48

44

40

35

55

LWA2, medium (dB(A))

29

41

46

43

43

44

46

43

53

LWA2, low (dB(A))

13

25

24

18

17

16

16

14

38

LWA5, high (dB(A))

19

33

39

46

48

44

42

36

52

LWA5, medium (dB(A))

13

24

28

41

35

31

26

18

51

LWA5, low (dB(A))

8

15

21

24

22

17

15

13

37

LWA6, high (dB(A))

19

33

39

46

48

44

42

36

52

LWA6, medium (dB(A))

13

24

28

41

35

31

26

18

43

LWA6, low (dB(A))

8

15

21

24

22

17

15

13

37

LWA2= housing sound power level in dB.

LWA5= free inlet sound power level in dB.

LWA6= free outlet sound power level in dB.

Accessories

WRG 300 WP - Accessories

Specific accessories

Product type Name Art. No. Price*(EUR) Action
Air filter, replacement ZF 300 0093.0696 on request
  • On the notes
Thermostat TH 10 0157.0764 on request
  • On the notes
Room air control RLS 1 No longer available for delivery 0157.0768 on request
  • On the notes

Product description

Productdescription

WRG 300 WP

short description

Compact ventilation system with heat recovery and heat pump

Product description

Features

  • 65% degree of heat provision.
  • WRG 300 WP: Plus re-heating of the supply air by means of an integrated heat pump.
  • WRG 300 WPK: Plus re-heating, or cooling if desired, of the supply air by means of an integrated heat pump.
  • Inner coating of heat resistant synthetic material, non-hygroscopic.
  • With two integrated filters, filter change is possible without tools.
  • 4 DN 150 duct connections on the upper side of the unit.
  • Hermetically sealed cooling circuit.
  • R134a coolant.
  • Heat pump operation only at ventilation step 2 = normal and 3 = high.
  • Vaporizer and capacitor made of copper tubes with aluminium lamella..
  • Recommended installation site is a cellar room.
  • WRG 300 WP: Housing made of galvanised sheet-steel; heat pump is dark grey.
  • WRG 300 WPK: Housing made of galvanised sheet-steel; heat pump is dark grey.
  • Main components for WP300 heat pump module: Compressor, condenser, evaporator, expansion valve, dryer, inspection window , Pressostat.
  • Evaporator and capacitor protrude from the side, suitable for pushing into WRG 300.
  • Compressor: Piston stroke compressor, 230 V AC, 50 Hz.

Heat exchanger

  • Aluminium counterflow plate heat exchanger.
  • The heat exchanger can be removed without tools.
  • Separate air flows, separation by means of aluminium plates.
  • The heat exchanger can be exchanged with the summer casssete SK 300 for operation in summer. No tools are required for exchange.
  • Easy cleaning of the heat exchanger with water and a mild detergent.

Anti-frost protection

  • The frost protection feature switches the supply air fan off when the outgoing air temperature is too low (< 4 °C).
  • The heat pump switches the compressor off when the outgoing air temperature is too low ( +0.5° C).
  • If the outgoing air rises to +0.5°C, the compressor automatically switches on again.
  • Always combine heat recovery systems with earth heat exchangers or electrical frost protection heating, in order to be able to guarantee trouble-free operation, even at very low temperatures. Furthermore, an earth heat exchanger guarantees additional heater power rating in winter and additional cooling power in summer.

Heat recovery fan

  • 2 centrifugal fans, one fan each for supply air and exhaust air.
  • Fans with centrifugal impellers curved to the front.
  • Thermal overload protection as standard feature.
  • 3 ventilation steps: 1 = economy setting, 2 = normal, 3 = high.

Mounting instructions

  • Housing covers can be unscrewed.
  • Connect air channels and condensation drainage prior to commissioning.
  • Recommended for installation in cellars or store rooms.
  • Sound absorbers on the inlet and outlet side are recommended.
  • Material: Sheet steel, galvanised
  • Use ELM flexible cuffs to prevent transfer of vibrations onto the duct system.

Electrical connection

  • When delivered, the device is assembled and ready for service.
  • WRG 300 WP: 3-core connection cable with safety plug.
  • WRG 300 WPK: 3-core connection cable, 1.5 m long.
  • WRG 300 WP: Controlled using RLS 1 accessories.
  • WRG 300 WPK: Thermostat controller (5° - 30° C) included in delivery.

Condensation drain

  • The condensation is drained at the condensation drainage fitted on the side of the unit.

Safety devices

  • Fan motor with thermal overload protection: The thermal contact switches off under thermal overload and comes on automatically again after cooling down.
  • Heat pump: HIgh-pressure protection (Pressostat) with reclosing lockout and RESET key.

Table of contents

Wiring diagram

WRG 300 WP - Wiring diagram

S1.1 System on, WRG 300 at step 1, WP300 off

S1.2 Main switch WP 300

S2 WRG 300 at step 2, WP 300 on

S3 WRG 300 at step 3, WP 300 on

TH10 Thermostat: Anti-frost protection fuse

R1 Outside air sensor (supply temperature). Installation: outside air duct, close to the outside wall / north side

WRG 300 heat recovery unit (1 = step 1 (economy), 2 = step 2 (middle), 3 = step 3 (high)

M1 Exhaust air fan

M2 Supply air fan

F1 Anti-frost protection fuse. In the WRG 300 system, this must be supplied by the customer, bridged to terminals M2 and M4. See WRG 300 wiring diagram

WP 300 Heat pump

F2 Pressostat (high pressure fuse)

F3 Anti-frost protection fuse (vaporiser)

M3 Compressor motor (with starting relay)

S1.1/1.2 Series switch / double rocker*

S2 Off 2-pole

S3 Off 2-pole

BU1 safety plug

V distributor (supplied by the customer)

* Two off-switches with indicator light can be used instead of a series switch with a double rocker





Predecessor - successor

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

On this website, technologies such as cookies and measurements of reach (targeting and tracking) are used (services). This means that personal information such as the IP address and browser information is processed to continuously improve our website as well as to display to you customised content that corresponds to your individual interests. You may of course influence the use of this information through the settings you choose. The settings you have chosen are stored in a necessary selection cookie. With the exception of the selection cookie mentioned above, technically non-essential cookies and measurements of reach are only used if you provide permission in advance by clicking “ACCEPT ALL AND CLOSE”. Details and options for customising your consent can be found under Data protection settings.

Here you can select a variety of different categories of services or cookies. By activating the corresponding “Statistics & analytics” checkbox and confirming “Save settings”, you can give your informed consent to the use of cookies for customisation purposes. At the bottom of the website under “Data protection settings”, you can change or revoke your consent and settings for the individual services at any time with effect for the future.

Necessary cookies are absolutely necessary for the operation of the website. Without these cookies, the website would not function properly.

These cookies and services collect and process data for statistics and analytics and thus enable further improvements of this website for users. Google Analytics and Google Adwords Conversion are used for this purpose. You will find a detailed description of such use in our Privacy Policy.

Save settings ACCEPT ALL AND CLOSE Data protection settings