A - WR 300 / WR 400 or RB 300 / RB 400 ventilation unit
A1 - Electronic slide-in module
A2 - Control circuit board
B1 - RLS 1 WR or RB-ZF4 room air control
B - RLS D1 WR or RB-D1-ZF4 room air control
W1 -230 VAC connecting cable
W2 - Shielded control cable (to be supplied by customer) for RLS D1 WR / RB-D1-ZF4 room air control. Room air control B (RLS D1 WR / RB-D1-ZF4) can also be connected instead of room air control B1 (RLS 1 WR /
RB-D1-ZF4). External diameter of the shielded cable 3.2...6.5 mm, e.g. LIYCY 2 x 0.75 mm².
W2' - Control cable (to be supplied by customer) for RLS 1 WR / RB-ZF4 room air control. External diameter of the control cable 3.2...6.5 mm, e.g. LIYY 6 x 0.34 mm²
S1 - Unit switch
M1 - Supply air fan
M2 - Exhaust air fan
S - Door contact switch/activated via front plate
T-min - Frost protection temperature sensor
S1 [blue] - setting potentiometer for supply air volumetric flow, ventilation level 1
S2 [blue] - setting potentiometer for supply air volumetric flow, ventilation level 2
S3 [blue] - setting potentiometer for supply air volumetric flow, ventilation level 3
S1 [red] - setting potentiometer for exhaust air volumetric flow, ventilation level 1
S2 [red] - setting potentiometer for exhaust air volumetric flow, ventilation level 2
S3 [red] - setting potentiometer for exhaust air volumetric flow, ventilation level 3
Jumper settings
J 1-3 - WR 300 (0,0,1) / WR 400 (0,1,0) unit type
J 4-5 - Frost protection temperature
J 6 - No function
J 7 - Time limitation (60 minutes) LS3 is activated
J 8 - RLS 1 WR or RLS D1 WR control unit is selected
J 9 - Humidity protection is blocked at switch position OFF Control unit: Switch setting OFF (standby) is
released
J 10 - 0 - 10V input for CO2 sensor blocked
Further connection options
W3 - Connecting cable (provided by customer) for external operating display.
k1- Potential-free relay contact k1 (max. 3 A / 250 VAC, 2 A / 30 VDC). Contact k1 is closed when the ventilation unit is running.
W4 - Connecting cable (to be supplied by customer) for external CO2/VOC sensor or external hygrostat. Hygrostat with potential-free contact.
W5 -Connecting cable (provided by customer) for external differential pressure controller. Differential pressure controller with potential-free relay contact. Minimum switching capacity of relay contact: 230 VAC / 2A. Remove J1 bridge on A2 control circuit board.